Specification:
range |
Acti 9
|
---|---|
product name |
Disbo iC60
|
product or component type |
Miniature circuit-breaker
|
device short name |
IC60N
|
poles description |
1P
|
number of protected poles |
1
|
[In] rated current |
2 A
|
network type |
AC
|
trip unit technology |
Thermal-magnetic
|
curve code |
C
|
breaking capacity |
50 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2 6 kA Icu at 72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
---|---|
[Ue] rated operational voltage |
240 V AC 50/60 Hz
|
magnetic tripping limit |
8 x In +/- 20 %
|
[Ics] rated service breaking capacity |
50 kA 100 % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC 6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DC |
limitation class |
3 conforming to EN/IEC 60947-2
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
contact position indicator |
Yes
|
control type |
Toggle
|
local signalling |
Trip indicator
|
mounting mode |
Clip-on
|
mounting support |
Rail
|
9 mm pitches |
2
|
height |
85 mm
|
width |
18 mm
|
depth |
78.5 mm
|
net weight |
0.125 kg
|
colour |
White
|
mechanical durability |
20000 cycles
|
electrical durability |
10000 cycles
|
provision for padlocking |
Padlockable
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
wire stripping length |
14 mm for top or bottom connection
|
tightening torque |
2 N.m top or bottom
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60947-2
EN/IEC 60898-1 |
---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
pollution degree |
3 conforming to EN/IEC 60947-2
|
tropicalisation |
2 conforming to IEC 60068-1
|
relative humidity |
95 % at 55 °C
|
ambient air temperature for operation |
-35…70 °C
|
ambient air temperature for storage |
-40…85 °C
|