Specification:
range of product |
Harmony XB4
|
---|---|
product or component type |
Push-button
|
device short name |
XB4
|
bezel material |
Chromium plated metal
|
fixing collar material |
Zamak
|
mounting diameter |
22 mm
|
sale per indivisible quantity |
1
|
shape of signaling unit head |
Round
|
type of operator |
spring return
|
operator profile |
Blue flush, unmarked
|
head type |
Standard
|
contacts type and composition |
1 NO
|
contact operation |
Slow-break
|
connections – terminals |
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22…2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1 |
height |
47 mm
|
---|---|
width |
30 mm
|
depth |
52 mm
|
terminals description ISO n°1 |
(13-14)NO
|
net weight |
0.08 kg
|
resistance to high pressure washer |
7000000 Pa at 55 °C, distance : 0.1 m
|
contacts usage |
Standard contacts
|
positive opening |
Without
|
operating travel |
2.6 mm (NO changing electrical state)
4.3 mm (total travel) |
operating force |
3.8 N NO changing electrical state
|
mechanical durability |
10000000 cycles
|
tightening torque |
0.8…1.2 N.m conforming to EN 60947-1
|
shape of screw head |
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver |
contacts material |
Silver alloy (Ag/Ni)
|
short-circuit protection |
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
|
[Ith] conventional free air thermal current |
10 A conforming to EN/IEC 60947-5-1
|
[Ui] rated insulation voltage |
600 V (pollution degree 3) conforming to EN/IEC 60947-1
|
[Uimp] rated impulse withstand voltage |
6 kV EN/IEC 60947-1
|
[Ie] rated operational current |
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1 |
electrical durability |
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
electrical reliability |
Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to EN/IEC 60947-5-4 |
device presentation |
Complete product
|
protective treatment |
TH
|
---|---|
ambient air temperature for storage |
-40…70 °C
|
ambient air temperature for operation |
-40…70 °C
|
overvoltage category |
Class I conforming to IEC 60536
|
IP degree of protection |
IP66 conforming to IEC 60529
IP67 IP69 IP69K |
NEMA degree of protection |
NEMA 13
NEMA 4X |
IK degree of protection |
IK06 conforming to IEC 50102
|
standards |
JIS C8201-5-1
EN/IEC 60947-5-1 EN/IEC 60947-1 UL 508 EN/IEC 60947-5-4 EN/IEC 60947-5-5 CSA C22.2 No 14 JIS C8201-1 |
product certifications |
UL listed
RINA BV LROS (Lloyds register of shipping) CSA DNV GL |
vibration resistance |
5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
|
shock resistance |
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27 |